Configuration3-wire — one current, one return, one compensation lead
Lead CompensationBridge-based compensation — assumes equal lead resistances
Residual ErrorZero if all 3 leads are same length and gauge; error = difference in lead R
Applicable ClassesIEC 60751 Class A, B, C (not Class AA)
Maximum Cable RunPractical to ~100 m when leads are matched and balanced
Connector TypesTerminal head, transmitter heads (DIN B), bare leads, M12
Element TypesPT100 (standard) or PT1000
Sheath Materials316 SS, 304 SS, Inconel 600, Hastelloy C-276
OD Range3.18 mm to 12.7 mm standard
DocumentationAS9100D COC standard; NIST cal on request
Technical Notes
Three-wire RTD is the dominant configuration in industrial process control, supported by virtually all DCS, PLC, and field transmitter manufacturers. The third wire allows the instrument to measure one lead resistance and subtract it from both current-carrying legs — this compensation is exact only if all three leads are the same resistance. For most installations using shielded cable run in conduit, this assumption holds well. For runs exceeding 100 m or where lead temperature varies significantly, 4-wire should be considered.